Steam Boiler Capacity Calculator (kg/h & kW)

Size your steam boiler in seconds: enter your steam demand or process heat load, working pressure, feedwater temperature and fuel type to get the required capacity, thermal output, standard boiler size and estimated fuel consumption.

Input Data

Steam tables (IAPWS-IF97)
kg/h
kW
bar(g)
°C
h/day
%

Results

Estimated
Required steam capacity (incl. margin)
-
kg/h
Thermal output
-
kW
Next standard boiler size
-
Steam demand without margin
-
Saturation temperature
-
Steam enthalpy, hg
-
Feedwater enthalpy, hfw
-
Heat per kg of steam
-
Fuel consumption (hourly)
-
Fuel consumption (daily)
-

Suggested Ekotek series

Request a Technical Proposal Our engineers will verify the sizing for your process.

How to Size a Steam Boiler

Choosing the right steam boiler capacity is the most important decision in any steam system project. An undersized boiler cannot hold pressure during peak demand, while an oversized one cycles on and off, wastes fuel and costs more to buy and install. Correct sizing starts with a clear picture of how much steam your process really needs, at what pressure and how the boiler will be fed.

Follow these steps to size a steam boiler:

  1. List all steam consumers. Collect the steam consumption of every heat exchanger, autoclave, dryer, cooker, sterilizer or humidifier in kg/h. If only the heat duty is known, use the process heat load in kW; the calculator converts it to kg/h using the steam tables.
  2. Apply a diversity factor. Not all consumers run at full load at the same time. Estimate the realistic simultaneous peak demand.
  3. Define the working pressure. The boiler must deliver steam at a pressure slightly higher than the highest pressure required by the consumers, allowing for pipe pressure losses. Higher pressure means higher saturation temperature and slightly higher enthalpy.
  4. Determine the feedwater temperature. With good condensate return and a feedwater tank, typical feedwater temperatures are 70–105 °C. Cold make-up water (10–20 °C) significantly increases the heat required per kilogram of steam.
  5. Add a safety margin. A margin of 10–20% covers start-up loads, piping heat losses, blowdown and modest future expansion.
  6. Select the next standard boiler size and a boiler type suitable for your fuel.

The Steam Boiler Capacity Formula

The heat that a boiler must transfer to the water is the difference between the enthalpy of the steam leaving the boiler and the enthalpy of the feedwater entering it:

Q [kW] = ṁ [kg/h] × (hg − hfw) [kJ/kg] / 3600

where ṁ is the steam mass flow, hg is the enthalpy of dry saturated steam at the working pressure, and hfw is the enthalpy of the feedwater. If you start from a heat load, the formula is rearranged: ṁ = Q × 3600 / (hg − hfw).

The fuel consumption follows from the thermal output, the boiler efficiency η and the lower heating value (LHV) of the fuel:

Fuel [unit/h] = Q [kW] / (η × LHV [kWh/unit])

Example Calculation

A dairy needs 5,000 kg/h of saturated steam at 10 bar(g), and the feedwater tank keeps the feedwater at 80 °C.

  • Absolute pressure: 10 + 1.013 = 11.01 bar(a), saturation temperature ≈ 184 °C
  • Steam enthalpy hg ≈ 2,780.7 kJ/kg
  • Feedwater enthalpy hfw at 80 °C ≈ 334.9 kJ/kg
  • Heat per kg: 2,780.7 − 334.9 = 2,445.8 kJ/kg
  • Thermal output: 5,000 × 2,445.8 / 3,600 ≈ 3,397 kW (3.4 MW)

With a 10% safety margin the design capacity becomes 5,500 kg/h, so the next standard boiler size is 6,000 kg/h. On natural gas (LHV 9.6 kWh/Nm³, efficiency 92%), a 5,500 kg/h load needs roughly 3,737 / (0.92 × 9.6) ≈ 423 Nm³/h.

Assumptions Used in This Calculator

FuelLower heating value (LHV)Typical boiler efficiencyUnit
Natural gas34.5 MJ/Nm³ (9.58 kWh/Nm³)92%Nm³
Diesel42.7 MJ/kg (11.86 kWh/kg), density 0.84 kg/L90%kg / L
Fuel oil (heavy)40.2 MJ/kg (11.17 kWh/kg)88%kg
Coal25.0 MJ/kg (6.94 kWh/kg)80%kg
Wood / biomass (~20% moisture)15.0 MJ/kg (4.17 kWh/kg)78%kg
Electric–98%kWh

Steam properties are taken from the IAPWS-IF97 steam tables for dry saturated steam between 1 and 25 bar(g) (atmospheric pressure 1.013 bar) with linear interpolation; feedwater enthalpy uses saturated-liquid values at the given temperature. Standard sizes used: 500, 750, 1,000, 1,500, 2,000, 2,500, 3,000, 4,000, 5,000, 6,000, 8,000, 10,000, 12,000, 15,000, 20,000, 25,000 and 30,000 kg/h. Blowdown, superheat, condensate flash steam and heat losses of the distribution network are not included. Results are indicative and do not replace a detailed engineering design.

Choosing the Right Ekotek Steam Boiler

Once the capacity is known, the fuel decides the boiler type. For natural gas, diesel and fuel oil, Ekotek's three-pass fire-tube Storm, Performance, Strong and Shield series offer high efficiency and compact footprints. For coal, wood and biomass, the Volcano, Grim, Thunderbolt and Hybrid series are designed for solid fuel combustion. Where emissions-free operation or small loads are required, the Mega Volt and Mega Volt X electric steam generators are an ideal choice. Browse all steam boilers or contact our engineers for a tailored proposal.

Frequently Asked Questions

How do I calculate the required steam boiler capacity?

Add up the steam consumption of all consumers in kg/h (or convert the process heat load in kW using kg/h = kW x 3600 / (hg - hf)), apply a diversity factor if not all consumers run simultaneously, then add a safety margin of typically 10-20% for start-up loads, heat losses and future expansion.

How many kW is 1 ton of steam per hour?

Depending on pressure and feedwater temperature, producing 1,000 kg/h of saturated steam requires roughly 620-700 kW of heat. At 10 bar(g) with 80 °C feedwater it is about 680 kW.

What is the difference between kg/h and "from and at 100 °C" ratings?

A "from and at 100 °C" (F&A) rating assumes feedwater at 100 °C and steam at atmospheric pressure (2257 kJ/kg). Real operating conditions require more heat per kg, so the actual output in kg/h is lower than the F&A rating. This calculator uses actual pressure and feedwater temperature.

Why does feedwater temperature matter?

Every degree of feedwater preheating reduces the heat the boiler must supply. Raising feedwater from 20 °C to 80 °C with a feedwater tank or economizer cuts the heat demand by about 10% and also reduces dissolved oxygen.

Should I oversize my steam boiler?

A moderate margin is recommended, but heavy oversizing causes frequent burner cycling, lower efficiency and higher investment cost. If the load varies strongly, two smaller boilers often perform better than one large unit.

Are the fuel consumption figures exact?

No. They are estimates based on typical lower heating values and boiler efficiencies. Actual consumption depends on fuel quality, burner tuning, load profile, blowdown and condensate return. Request a technical proposal for a project-specific calculation.